企業について Why Do Instruments and Meters Need Lightning Protection Grounding?

Why Do Instruments and Meters Need Lightning Protection Grounding?

2026-11-06

Instrument lightning protection grounding is mainly to guard against induced lightning. When lightning strikes nearby, long cables act like antennas and induce instantaneous high voltage, which can break through the instrument's chips.

最新の会社の事例について Why Do Instruments and Meters Need Lightning Protection Grounding?  0最新の会社の事例について Why Do Instruments and Meters Need Lightning Protection Grounding?  1最新の会社の事例について Why Do Instruments and Meters Need Lightning Protection Grounding?  2最新の会社の事例について Why Do Instruments and Meters Need Lightning Protection Grounding?  3
On-site damage commonly appears in three forms: data jumps, communication interruptions, and module burnout. The electronic components in industrial instruments typically have low voltage tolerance—a few thousand volts of surge is enough to cause a fault.

最新の会社の事例について Why Do Instruments and Meters Need Lightning Protection Grounding?  4最新の会社の事例について Why Do Instruments and Meters Need Lightning Protection Grounding?  5最新の会社の事例について Why Do Instruments and Meters Need Lightning Protection Grounding?  6最新の会社の事例について Why Do Instruments and Meters Need Lightning Protection Grounding?  7
It mainly relies on three coordinated measures:
●SPD Current Diversion — Installed on power lines and signal lines, it quickly conducts when a surge arrives, directing the current to the grounding busbar.
●Equipotential Bonding — Bond the instrument housing, cable trays, pipes, and cabinets together. When lightning strikes, all components rise in potential together, reducing the risk of mutual breakdown.

最新の会社の事例について Why Do Instruments and Meters Need Lightning Protection Grounding?  8最新の会社の事例について Why Do Instruments and Meters Need Lightning Protection Grounding?  9最新の会社の事例について Why Do Instruments and Meters Need Lightning Protection Grounding?  10最新の会社の事例について Why Do Instruments and Meters Need Lightning Protection Grounding?  11
●Shielding and Grounding — Metal cable trays, conduit pipes, and cable shielding layers must be continuously conductive and connected to a unified grounding system.

最新の会社の事例について Why Do Instruments and Meters Need Lightning Protection Grounding?  12最新の会社の事例について Why Do Instruments and Meters Need Lightning Protection Grounding?  13最新の会社の事例について Why Do Instruments and Meters Need Lightning Protection Grounding?  14最新の会社の事例について Why Do Instruments and Meters Need Lightning Protection Grounding?  15
Where failures most often occur:
●Ground wires that are too long — SPD grounding wires should generally be kept within 0.5 meters. Excessive length generates additional voltage, and the residual voltage may exceed the instrument's tolerance.
●Focusing only on grounding resistance — A qualified resistance only indicates a good DC path. The connection path during a lightning strike is equally critical.

最新の会社の事例について Why Do Instruments and Meters Need Lightning Protection Grounding?  16最新の会社の事例について Why Do Instruments and Meters Need Lightning Protection Grounding?  17最新の会社の事例について Why Do Instruments and Meters Need Lightning Protection Grounding?  18最新の会社の事例について Why Do Instruments and Meters Need Lightning Protection Grounding?  19
●Complete isolation of different grounds — During a lightning strike, a high potential difference can appear between different grounds, making equipment breakdown more likely.
●Cable trays broken midway — Loose connections, paint, or corrosion can break electrical contact, weakening the shielding effect.
So, effective lightning protection grounding means giving surges a short and reliable path while keeping all related metal parts at roughly the same potential.

最新の会社の事例について Why Do Instruments and Meters Need Lightning Protection Grounding?  20最新の会社の事例について Why Do Instruments and Meters Need Lightning Protection Grounding?  21最新の会社の事例について Why Do Instruments and Meters Need Lightning Protection Grounding?  22最新の会社の事例について Why Do Instruments and Meters Need Lightning Protection Grounding?  23